porate both transit-time and Doppler
capabilities, enabling users to make all
required measurements with one unit.
Multiple Applications
Since they can be installed anywhere along district energy distribution
pipelines, clamp-on ultrasonic flow
meters have the flexibility to be used to
balance a hot or chilled-water system,
improve chiller performance, indicate
direction of flow, or measure thermal
energy use.
These meters can be used
to balance a hot or chilled-water system, improve chiller
performance or measure
thermal energy use.
Balancing Flows
Prior to clamp-on flow meters and
transit-time technology, balancing flows
throughout a building was done by only
reading flows at the circuit-balancing
valve. The balancing valves provide
pressure taps, and a differential pressure manometer is used for proportional flow correlation. One disadvantage
of balancing valves is that they are not
always located on the line where critical
measurements need to be made.
Portable clamp-on meters, however,
may be used anywhere on the line, and
dual-channel models are able to measure two pipes simultaneously. These
units can be used to balance systems as
well as to verify a hot or chilled-water
system’s overall performance. Using
measurements taken at various locations along the heating or cooling loop,
system operators can ensure that energy
is distributed properly. When this is the
case, systems often find they can reduce
their hot and chilled-water production
– saving energy and operating costs, as
well as reducing the need for additional
maintenance and/or equipment.
In district cooling plants, channel
one can measure the chilled water while
channel two measures condenser water.
This information enables operators to
regulate the flow to design conditions.
In cases where a main pipe is not accessible, measurements may be taken on
two branches, which the meter can
then add to get the total flow in the
main. For a two-branch system, flow
can be calculated by measuring main
flow and subtracting the flow of branch
one from that of branch two. Another
example would be measuring the primary, secondary and tertiary flows of a
decoupled chiller system. The clamp-on
technology can be used very effectively
to indicate direction and flow rate of
the decoupled crossover connection.
In hot water district heating systems, clamp-on meters can measure the
output flow of two boilers simultaneously to balance them. They can also
measure the recirculation loop on boilers to ensure that minimum design flow
requirements are met; flow below the
minimum design standard can possibly
cause damage to the boiler.
Improving Chiller
Performance
In addition to balancing systems,
the clamp-on meter’s ability to measure
two pipes simultaneously makes it useful in assessing how well a chiller/heat
exchanger is performing and whether
work needs to be done on it to improve
efficiency. This is done by measuring
the condenser and evaporator flows and
temperature using clamp-on transducers
and resistance temperature detectors in
the flow meter.
In the Siemens Sitrans FUE series
of clamp-on meters, the flow and temperature measurements, along with a
kilowatt input, provide operators with a
coefficient of performance and energy
efficiency ratings. The data can be used
to compare chiller performance before
and after any maintenance is done,
which will indicate how much improvement has been made.
Measuring Thermal
Energy Use
Clamp-on ultrasonic flow meters
can also be used to measure hot or
chilled-water use for billing purposes.
District energy plants can meter the
consumption of customer buildings,
and building owners can submeter their
tenants’ thermal energy use as well, by
floor. The advantage to billing based
on each customer’s or tenant’s energy
use (as opposed to by square footage
or apportionment) is that it allows their
individual consumption levels to be
projected – which better enables energy
consumers to become aware of and curb
unnecessary energy use.
In these instances, a permanent
revenue-grade unit would be used that
measures the flow rate along with the
supply and return temperature to calculate Btus. This type of meter is wall-mountable and provides an analog or
digital output of Btu or tons. A portable
clamp-on meter can be used in addition
to verify the accuracy of permanent
meter readings.
The temperature sensors are avail-
able as clamp-on or insert types and are
precision-matched to 0.02 degree F pro-
viding a highly accurate delta T reading.
Thermal energy measurements are eas-
ily made as the flow and temperature
elements are ‘nonintrusive.’
With their versatility in these vari-
ous applications, clamp-on ultrasonic
flow meters can be useful in commis-
sioning or recommissioning build-
ings or district energy systems, as
well as in helping buildings achieve
LEED® (Leadership in Energy and
Environmental Design) Green Building
Rating System™ certification. In the
LEED system, the measurement of
hot and chilled-water system flow is
required for a building to earn points
in the Energy and Atmosphere –
Measurement and Verification credit
category (EAc5) for both existing and
new construction. Buildings must
provide measurements demonstrat-
ing chiller efficiency, boiler efficiency,
flows, building usage, and the amount
of energy used to produce heating or
cooling (kilowatts per ton).
Case Study:
The Country Club
The clamp-on ultrasonic flow meter
indeed proved to be instrumental in
optimizing the geothermal district
heating system at the upscale New